2021-05-24 13:58:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) 1A) SHEET A 1 - CORRIDOR WALL RATING
  
 THERE APPEARS A WALL TYPE INDICATED WITH A SQUARE
 AROUND AN A BUT NO INDICATION OF TYPE OF THAT IT IS
 SMOKE RATED.
  
 YOUR RESPONSE INDICATED THAT THE CORRIDORS NEED NOT BE
 RATED DUE TO THE FA & FS SYSTEMS; HOWEVER, (2) (A)
 REQUIRES A SMOKE RATING.
  
  
 (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.7:
 (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT
 SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 8.4.
  
  
 PLEASE PROVIDE DETAILS OF THE SMOKE RATING.
  
  
 2) 4) SHEET CS 1 & LS 1 - THERE IS INDICATION OF A FIRE
 SPRINKLER SYSTEM TO BE INSTALLED.
  
 PER FAC FIRE SPRINKLER DOCUMENTS SHALL BE SUBMITTED BY
 AN EOR WITH THIS MASTER PERMIT.
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 THIS PERMIT WILL NPT BE APPROVED WITHOUT FIRE SPRINKLER
 DOCUMENTS PER FAC. A FULL SPRINKLER PLAN SET IS NOT
 NECASSARILY REQUIRED. A SIGNED AND SEALED DOCUMENT WITH
 A WRITTEN NARRATIVE OR BULLET POINTS OF ALL THE FAC
 REQUIRMENTS IS ALL THAT IS REQUIRED WITH THIS MASTER
 PERMIT.
  
 PLEASE REVIEW AND PROVIDE SIGNED AND SEALED DOCUMENTS
 PER FAC.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL