2021-06-03 14:23:46 | DAYCARE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) FBC 466.8 CORRIDORS. IN BUILDINGS PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND |
| 903.3.1.1 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE |
| RATED, PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS |
| IN ACCORDANCE WITH SECTION 710. |
| 2) PLEASE SHOW THAT THE EXISTING CORRIDOR WALLS MEET |
| THE REQUIREMENTS OF SMOKE PARTITIONS - FBC 710.4 |
| CONTINUITY. |
| SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE |
| FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR |
| OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE |
| UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING |
| MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. |
| 3) RESTROOMS FOR AGE GROUP 3 & 4 = ADA RESTROOM PAPER |
| TOWEL DISPENSER - THE OUTLET OF THE DISPENSER SHOULD BE |
| SHOWN TO MEET THE REACH RANGES SEE FBC ACCESSIBILITY |
| 308.1 (SEE ALSO THE ADVISORY FOR AGE GROUPS) - DRAWING |
| P-1 "RESTROOM REFERENCE NOTES" NOTE NUMBER 1 SHOWS THE |
| LOW REACH AT 15" - SHOULD BE 20". - THIS SHOULD ALSO BE |
| SHOWN ON DRAWING A-1 |
| 4) PRODUCT APPROVAL (FL14237-R3) FOR THE EXTERIOR DOOR |
| HAS EXPIRED - PLEASE PROVIDE THE UPDATED VERSION |
| (FL14237-R5) FRONT PAGES AND THE INSTALLATION |
| INSTRUCTIONS. DOOR PRODUCT APPROVAL NEEDS TO BE |
| REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE |
| DRAWINGS. |
| 5) PLEASE SHOW THAT CLOSURES ARE REQUIRED FOR THE EXIT |
| DOORS - FBC 466.4 DOOR CLOSURE. |
| ANY EXIT DOOR DESIGNED TO BE NORMALLY CLOSED SHALL BE |
| KEPT CLOSED AND SHALL COMPLY WITH SECTION 716.5. |
| 6) PLEASE SHOW WALL FINISH AT THE MOP SINK TO COMPLY |
| WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE) |
| 7) LIFE SAFETY PLAN STILL SHOWS BUILDING CONSTRUCTION |
| TYPE AS (IV) - SHOULD BE SHOWN AS (VB). |
| |