2021-04-29 14:30:17 | REVISIONS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTH ENDS OF |
| THE RAMPS TO COMPLY WITH FBC 505.10.1 RAMP HANDRAILS |
| SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12 |
| INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF |
| RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL, GUARD, OR |
| THE LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE |
| HANDRAIL OF AN ADJACENT RAMP RUN. |
| 2) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT TOP OF ALL |
| STAIR TO COMPLY WITH FBC 505.10.2 AT THE TOP OF A STAIR |
| FLIGHT, HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE |
| LANDING FOR 12 INCHES (305 MM) MINIMUM BEGINNING |
| DIRECTLY ABOVE THE FIRST RISER NOSING. EXTENSIONS SHALL |
| RETURN TO A WALL, GUARD, OR THE LANDING SURFACE, OR |
| SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT |
| STAIR FLIGHT. |
| 3) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTTOM OF ALL |
| STAIR TO COMPLY WITH FBC 505.10.3 AT THE BOTTOM OF A |
| STAIR FLIGHT, HANDRAILS SHALL EXTEND AT THE SLOPE OF |
| THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST |
| EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING. |
| EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE LANDING |
| SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT STAIR FLIGHT. |
| 4) HANDRAILS SHALL BE SHOWN ON BOTH SIDES OF RAMPS AND |
| STAIR PER FBC 1011.11 AND FBC 1012.8 |
| 5) DRAWING A2.0 - DOORS BETWEEN UNITS IN THE CORRIDOR |
| WERE TO SWING IN PER APPROVED DRAWINGS AS TO NOT |
| ENCROACH IN THE EGRESS PATH FBC 1005.7.1 - DOOR SWING |
| ON ALL OTHER PLANS SHOULD MATCH. |