Plan Review Notes
Plan Review Notes For Permit 21031452
Permit Number 21031452
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-29 14:30:17REVISIONS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTH ENDS OF
 THE RAMPS TO COMPLY WITH FBC 505.10.1 RAMP HANDRAILS
 SHALL EXTEND HORIZONTALLY ABOVE THE LANDING FOR 12
 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. EXTENSIONS SHALL RETURN TO A WALL, GUARD, OR
 THE LANDING SURFACE, OR SHALL BE CONTINUOUS TO THE
 HANDRAIL OF AN ADJACENT RAMP RUN.
 2) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT TOP OF ALL
 STAIR TO COMPLY WITH FBC 505.10.2 AT THE TOP OF A STAIR
 FLIGHT, HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEGINNING
 DIRECTLY ABOVE THE FIRST RISER NOSING. EXTENSIONS SHALL
 RETURN TO A WALL, GUARD, OR THE LANDING SURFACE, OR
 SHALL BE CONTINUOUS TO THE HANDRAIL OF AN ADJACENT
 STAIR FLIGHT.
 3) HANDRAIL EXTENSIONS SHOULD BE SHOWN AT BOTTOM OF ALL
 STAIR TO COMPLY WITH FBC 505.10.3 AT THE BOTTOM OF A
 STAIR FLIGHT, HANDRAILS SHALL EXTEND AT THE SLOPE OF
 THE STAIR FLIGHT FOR A HORIZONTAL DISTANCE AT LEAST
 EQUAL TO ONE TREAD DEPTH BEYOND THE LAST RISER NOSING.
 EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE LANDING
 SURFACE, OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT.
 4) HANDRAILS SHALL BE SHOWN ON BOTH SIDES OF RAMPS AND
 STAIR PER FBC 1011.11 AND FBC 1012.8
 5) DRAWING A2.0 - DOORS BETWEEN UNITS IN THE CORRIDOR
 WERE TO SWING IN PER APPROVED DRAWINGS AS TO NOT
 ENCROACH IN THE EGRESS PATH FBC 1005.7.1 - DOOR SWING
 ON ALL OTHER PLANS SHOULD MATCH.