2021-05-07 13:24:07 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE ROOF SHEATHING ATTACHMENT. FBC |
| R803.2.3.1 |
| 2) PLEASE PROVIDE A SITE PLAN FBC 107.2.5 SITE PLAN. |
| THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE |
| APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE |
| PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT |
| SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) |
| 3) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING |
| THE FLOOD ZONE BASED ON THE LATEST FIRM. |
| 4) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE |
| LISTED ON THE DRAWINGS BY THE PRODUCT APPROVAL NUMBERS. |
| 5) STRUCTURAL DRAWINGS NEED TO BE SIGNED BY THE |
| ENGINEER. |
| FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR - |
| IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN |
| ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN MAIL IN OR |
| DROP OFF THE ORIGINAL SIGNED AND SEALED |
| DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING |
| DEPT. AT THE CITY HALL |