Plan Review Notes
Plan Review Notes For Permit 21031428
Permit Number 21031428
Review Stop B
Sequence Number 2
Notes
Date Text
2021-05-24 14:14:10PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT COMPLIED. THE NEW WINDLOAD CALCULATIONS FROM
 THE ENGINEER ARE FOR EXPOSURE CATEGORY C. THIS
 STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D.] THE
 WINDLOAD CHART IS FOR EXPOSURE CATEGORY C AND THIS
 PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH A 170
 MPH WINDSPEED. PLEASE CORRECT. FBC 1609
  
 2) [NOT COMPLIED. THE LOCATIONS OF THE OPENINGS FROM
 THE BUILDING'S CORNERS WERE NOT PROVIDED.] THE
 PRESSURES THAT ARE MARKED IN THE WINDLOAD TABLE ARE FOR
 INTERIOR WALL ZONE 4. THE WINDLOAD PRESSURES FOR THE
 ZONE 5 CORNER AREAS ARE SIGNIFICANTLY MORE. SPECIFY THE
 LOCATION OF THE OPENINGS FROM THE CORNER OF THE
 BUILDING. USE THE BUILDINGS HEIGHT AND THE SMALLER OF
 THE WALL LENGTHS TO DETERMINE THE WIDTH OF ZONE 5 FROM
 THE CORNER OF THE BUILDING IN THE CHART BELOW THE
 WINDLOAD CHART. FBC AMENDMENTS 107.2.1 AND FBC 1609