Plan Review Notes For Permit 21031428 |
Permit Number |
21031428 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-05-24 14:14:10 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) [NOT COMPLIED. THE NEW WINDLOAD CALCULATIONS FROM | | THE ENGINEER ARE FOR EXPOSURE CATEGORY C. THIS | | STRUCTURE IS LOCATED IN EXPOSURE CATEGORY D.] THE | | WINDLOAD CHART IS FOR EXPOSURE CATEGORY C AND THIS | | PROJECT IS LOCATED IN EXPOSURE CATEGORY D WITH A 170 | | MPH WINDSPEED. PLEASE CORRECT. FBC 1609 | | | | 2) [NOT COMPLIED. THE LOCATIONS OF THE OPENINGS FROM | | THE BUILDING'S CORNERS WERE NOT PROVIDED.] THE | | PRESSURES THAT ARE MARKED IN THE WINDLOAD TABLE ARE FOR | | INTERIOR WALL ZONE 4. THE WINDLOAD PRESSURES FOR THE | | ZONE 5 CORNER AREAS ARE SIGNIFICANTLY MORE. SPECIFY THE | | LOCATION OF THE OPENINGS FROM THE CORNER OF THE | | BUILDING. USE THE BUILDINGS HEIGHT AND THE SMALLER OF | | THE WALL LENGTHS TO DETERMINE THE WIDTH OF ZONE 5 FROM | | THE CORNER OF THE BUILDING IN THE CHART BELOW THE | | WINDLOAD CHART. FBC AMENDMENTS 107.2.1 AND FBC 1609 |
|