Plan Review Notes For Permit 21031423 |
Permit Number |
21031423 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-15 14:37:44 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT PRODUCT APPROVAL FOR THE STRUCTURAL MULLIONS. | | FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR | | THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001. | | PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA | | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM | | DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING | | MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL MULLIONS | | AND EXTERIOR DOOR TYPES. ONLY ONE SET IS REQUIRED TO BE | | UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS. | | | | 2) THE PRODUCT APPROVALS FOR THE FIXED WINDOWS (NOA NO. | | 17-1218.12) AND THE GLAZED DOORS (NOA NO. 16-0617.03) | | HAVE NOT BEEN CONFIRMED TO COMPLY WITH THE 2020 FBC | | SEVENTH EDITION. SUBMIT CURRENT PRODUCT APPROVALS. FBC | | 107.3.4 | | | | 3) IN THE WINDOW AND DOOR SCHEDULE, THE HORIZONTAL | | ROLLING WINDOWS DESIGN PRESSURES ARE + OR - 65 PSF. THE | | REQUIRED PRESSURES IN THE SCHEDULE ARE +49.8 PSF AND - | | 66.6 PSF. THE REQUIRED NEGATIVE PRESSURE -66.6 PSF CAN | | NOT BE MORE THAN THE DESIGN PRESSURE -65 PSF. FBC-R301 | | | | |
|