2021-07-02 09:40:02 | CONDO REMODEL |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) DOCUMENT LABELED "TRUMP PLAZA GHP4 CALCS |
| (06.21.2021) - SS.PDF" WINDOW / DOOR CALCULATIONS SHOW |
| THAT SOME OF THE PRODUCT APPROVALS PROVIDED DO NOT MEET |
| THE REQUIRED PRESSURES. A COMMENT ON THE CALCULATIONS |
| SAY THAT IT IS OK TO BE WITHIN 5% OF THE DESIGN |
| PRESSURE - PLEASE HAVE THE ENGINEER EXPLAIN IN WRITING |
| WHERE THAT IS ALLOWED PER THE FBC |
| 2) PRODUCT APPROVALS NEED TO MEET THE REQUIRED DESIGN |
| LOADS FBC 1609.1.1 |
| 3) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED |
| SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE |
| CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. |
| FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT |
| ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |