Plan Review Notes
Plan Review Notes For Permit 21031397
Permit Number 21031397
Review Stop B
Sequence Number 3
Notes
Date Text
2021-06-22 12:21:54CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL FOR THE SWING DOOR NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 FBC WPB 107.3.4
 2) PLEASE PROVIDE A WINDOW AND DOOR SCHEDULE SHOWING
 THE SIZES AND TYPES OF EXTERIOR WINDOWS AND DOORS.
 3) FLOORING TEST REPORTS PROVIDED SHOW A DROP CEILING
 AS PART OF THE ASSEMBLY TESTED. (EXISTING BUILDING MAY
 NOT HAVE A DROP CEILING SIMULAR TO THE TEST REPORT).
 4) FLOORING TEST REPORTS PROVIDED ARE FOR AN 8"
 CONCRETE SLAB - PLEASE HAVE THE DESIGNER STATE ON THE
 DRAWINGS THE THICKNESS OF THE EXISTING CONCRETE SLAB OR
 THE DESIGNER CAN REVIEW AND MARK THE TEST REPORTS
 APPROVED FBC WPB 107.3.4
  
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: FOR
 THE NEW TILE FLOOORING
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  
  