2021-04-20 11:30:0704/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING RISER DIAGRAM REQUIRED FOR
 THE AREAS WHERE CHANGES ARE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 2. THE 2017 6TH EDITION IS REFERENCED ON THE TITLE
 SHEET, AND ON THE MEP PAGE, THE 2020 7TH EDITION IS
 REFERENCED. PLEASE CORRECT PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ON THIS PAGE, THERE ARE ACCECIBLITY NOTES
 WHICH ARE NOT REQUIRED FOR A UNIT IN A BUILDING IN THE
 BATHROOM, SO PLEASE DELETE THEM IF THEY DON?T PERTAIN
 TO THIS RENOVATION FOR FIELD CLARITY.
  
 3. WHERE OR IF THE FLOOR WILL BE CUT TO ACCOMMODATE
 PIPING, PLEASE PROVIDE DETAIL FOR THE REPAIR OF THE
 CONCRETE DECK PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
 5.
  
 6. SUGGESTED VERBIAGE FOR SHOWER PAN PER THE 2020 FBC
 SECTION P 421.5.2 SHOWER LINING. FLOORS UNDER SHOWER
 COMPARTMENTS, EXCEPT WHERE PREFABRICATED RECEPTORS HAVE
 BEEN PROVIDED, SHALL BE LINED AND MADE WATER TIGHT
 UTILIZING MATERIAL COMPLYING WITH SECTIONS 421.5.2.1
 THROUGH 421.5.2.6. SUCH LINERS SHALL TURN UP ON ALL
 SIDES NOT LESS THAN 2 INCHES (51 MM) ABOVE THE FINISHED
 THRESHOLD LEVEL. LINERS SHALL BE RECESSED AND FASTENED
 TO AN APPROVED BACKING SO AS NOT TO OCCUPY THE SPACE
 REQUIRED FOR WALL COVERING, AND SHALL NOT BE NAILED OR
 PERFORATED AT ANY POINT LESS THAN 1 INCH (25 MM) ABOVE
 THE FINISHED THRESHOLD. LINERS SHALL BE PITCHED
 ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAINS AND BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET. THE COMPLETED
 LINER SHALL BE TESTED IN ACCORDANCE WITH SECTION 312.9.
  
 7. SUGGESTED VERBIAGE FOR TUBS VALVES PER THE 2020 FBC
 SECTION P 412.5 BATHTUB AND WHIRLPOOL BATHTUB VALVES.
 THE HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL
 BATHTUBS SHALL BE LIMITED TO A MAXIMUM TEMPERATURE OF
 120?F (49?C) BY A WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION 412.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  