Plan Review Notes
Plan Review Notes For Permit 21031397
Permit Number 21031397
Review Stop E
Sequence Number 1
Notes
Date Text
2021-04-19 15:37:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) RISER SHOWS 250A FUSES ON 4/0 NEEDS TO BE 225A FUSES
 OR 250 KCMIL WIRE.
  
 2) WEST SIDE BALCONIES REQUIRE OUTLETS WP/GFCI. 210.52