Plan Review Notes For Permit 21031397 |
Permit Number |
21031397 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-19 15:37:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | 1) RISER SHOWS 250A FUSES ON 4/0 NEEDS TO BE 225A FUSES | | OR 250 KCMIL WIRE. | | | | 2) WEST SIDE BALCONIES REQUIRE OUTLETS WP/GFCI. 210.52 |
|