2021-04-19 12:01:53 | CONDO REMODEL |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT |
| APPROVAL FOR THE NEW EXTERIOR SWING DOORS. |
| 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE ARCHITECT OF RECORD. |
| 3) ALL DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER WHO DESIGNED THEM. FBC WPB 107.1 |
| 4) PLEASE SHOW WALL FRAMING DETAILS AND MATERIAL TO |
| COMPLY WITH FBC 603 |
| 5) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE SHOW |
| DESIGN PER THE CODE IN EFFECT (FBC 2020 USING ASCE |
| 7-16) |
| 6) PLEASE SHOW THE ELEVATOR HOISTWAY PROTECTION PER FBC |
| 3006.3 |
| 7) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| FOR THE NEW TILE FLOOORING |
| |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| ATTACHED TO THE FLOORING) |
| |