2021-04-07 17:54:15 | 04/07/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR POOL HEATER GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. |
| G2408.1. |
| |
| 2. THE CITY HAS A RECORD OF AN EXISTING GAS METER |
| CONNECTED TO AN EXISTING POOL HEATER. IS THIS METER |
| REPLACING THE OLD SYSTEM, AND IS SO THE BTU LOAD OF THE |
| EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM |
| MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. |
| SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE |
| OF EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, |
| THE PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND |
| THE DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE |
| POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE |
| LOAD OF THE SECTION. NOTE: IF THE EXISTING SYSTEM IS |
| LESS THAN A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS |
| INCREASED TO 2 PSI, A LINE PRESSURE REGULATOR IS |
| REQUIRED AT ALL THE EXISTING APPLIANCES PER THE 2020 |
| FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2, |
| G2413.3. |
| |
| NOTE IF THIS IS A NEW METER, CLARIFY AND PUT ON PLANS A |
| SECOND NEW METER. |
| |
| 3. A REGULATOR MAY BE REQUIRED TO BRING THE SYSTEM DOWN |
| TO 10.5 WC. PLEASE SUBMIT THE MANUFACTURER?S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| G2421.1. |
| |
| 4. PLEASE LABEL AND SHOW ALL SHUT-OFF, DRIP LEG, AND |
| UNIONS IN FRONT OF REGULATOR 1? OF EITHER SIDE PER THE |
| 2020 FBC RES. SEC G2421.2. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |