Plan Review Notes
Plan Review Notes For Permit 21031267
Permit Number 21031267
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-07 17:54:1504/07/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR POOL HEATER GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC RES. SEC.
 G2408.1.
  
 2. THE CITY HAS A RECORD OF AN EXISTING GAS METER
 CONNECTED TO AN EXISTING POOL HEATER. IS THIS METER
 REPLACING THE OLD SYSTEM, AND IS SO THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM
 MUST BE REDONE TO ENSURE A SAFE OPERATING SYSTEM.
 SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE
 OF EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE,
 THE PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND
 THE DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE
 POINT OF DELIVERY TO THE MOST REMOTE OUTLET AND THE
 LOAD OF THE SECTION. NOTE: IF THE EXISTING SYSTEM IS
 LESS THAN A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS
 INCREASED TO 2 PSI, A LINE PRESSURE REGULATOR IS
 REQUIRED AT ALL THE EXISTING APPLIANCES PER THE 2020
 FBC RES. SECS. G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 NOTE IF THIS IS A NEW METER, CLARIFY AND PUT ON PLANS A
 SECOND NEW METER.
  
 3. A REGULATOR MAY BE REQUIRED TO BRING THE SYSTEM DOWN
 TO 10.5 WC. PLEASE SUBMIT THE MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1.
  
 4. PLEASE LABEL AND SHOW ALL SHUT-OFF, DRIP LEG, AND
 UNIONS IN FRONT OF REGULATOR 1? OF EITHER SIDE PER THE
 2020 FBC RES. SEC G2421.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved