Plan Review Notes For Permit 21031266 |
Permit Number |
21031266 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-04-09 12:32:55 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00 | | PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-5; | | EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); | | ULTIMATE WIND SPEED (180), IS NOT CORRECT. THE CORRECT | | EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D, THE | | CORRECT SYSTEM IS W-3. | | 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 | | CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED | | HIP & RIDGE METAL TO BE INSTALLED. WHEN USING METAL A | | PRODUCT APPROVAL/NOA IS REQUIRED. EXAMPLE FL5374-R6. | | |
|