2021-04-22 16:38:40 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21031243 |
| 4/22/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE GAS PLANS INCLUDING A GAS PIPING RISER, |
| COMBUSTION AIR CALCULATIONS AND VENTING PLANS- SECTIONS |
| 107.2.1, 107.3.5.3 WPB AND FBC RES. FUEL GAS. |
| |
| 2) GAS RISER SHALL INCLUDE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) LOCATION OF METER OR LP TANK(S) AND1ST STAGE |
| DELIVERY PRESSURE. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF 2ND STAGE REGULATORS, SHUTOFF VALVES, |
| AND PIPE UNIONS. |
| H) INLET AND OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES OR PIPE SIZING METHOD USED. |
| |
| 3) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW |
| THE AIR WILL BE PROVIDED TO THE GAS RANGE- SECTION- |
| G2407.1 FBC RES. |
| |
| 4) PROVIDE MAKEUP AIR FOR THE DRYER AND INDICATE HOW |
| THE MAKEUP AIR WILL BE PROVIDED- G2439.5 FBC RES. |
| |
| 5) PROVIDE EQUIPMENT SCHEDULES FOR THE TANKLESS WATER |
| HEATERS INDICATING MAKES AND MODELS, BTU CAPACITIES, |
| AND EFFICIENCY RATING PER TABLE C404.1 FBC EC. |
| |
| 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| FIRED APPLIANCES- SECTION G2408.1 FBC RES. |
| |
| 7) SUBMIT A GAS SUB-PERMIT IF THE INSTALLATIONS ARE TO |
| BE INCLUDED UNDER THE MASTER PERMIT- SECTION 105.1 WPB. |
| IF THE GAS INSTALLATIONS ARE TO BE UNDER A SEPARATE |
| PRIMARY PERMIT, PLEASE PLACE A NOTE ON THE PLAN. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |