2021-06-14 09:27:21 | SIGNATURE REVIEW |
| DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE |
| READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED |
| TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER |
| OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR |
| - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN |
| ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE |
| ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE |
| FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL. |
| |
2021-06-04 06:55:52 | SEE FIRST CYCLE COMMENTS. |
| |
| 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-21031226 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SHOW THE CORRECT LOCATION UNDER DESIGN |
| INFORMATION (WEST PALM BEACH) ON THE MECHANICAL |
| EQUIPMENT SIZING CALCULATIONS. |
| |
| 2) AN ENGINEER MUST DIGITALLY SIGN AND SEAL OR THE |
| MECHANICAL CONTRACTOR HOLDING THE PERMIT TO INSTALL THE |
| EQUIPMENT FOR THIS PROJECT MUST PRINT THEIR NAME AND |
| SIGN THEIR NAME ON THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. F.S. 471.003(H) |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |