Plan Review Notes For Permit 21031226 |
Permit Number |
21031226 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-06-14 09:24:36 | NEW SFR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) DRAWING A4 SHOWS THE WIND SPEED FOR DESIGN AT 160 | | MPH - WIND SPEED SHOULD BE 170 MPH PER FBC WPB SECTION | | 120 | | 2) DRAWING A2 DOOR AND WINDOW SCHEDULE IS NOT CORRECT | | DOOR NUMBER 4 IS MISSING - OPENING NUMBER 3 SHOWS A | | DOOR IN PLACE OF A WINDOW (PLEASE CORRECT THE WINDOW | | AND DOOR SCHEDULE) | | 3) PLEASE PROVIDE THE FRONT PAGE OF THE FLORIDA STATE | | PRODUCT APPROVAL FOR THE DOOR. | | 4) ALL PRODUCT APPROVALS SHOULD BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | 107.3.4 | | | | | | | | | | |
|