Plan Review Notes
Plan Review Notes For Permit 21031226
Permit Number 21031226
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-14 12:46:001ST REVIEW FBC-2020 RES.
 PERMIT- 21031226
 4/14/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: THE PLAN SHEET DOES NOT BEAR THE NAME,
 TITLE BLOCK, SIGNATURE OR SEAL OF THE PERSON WHO
 PREPARED THE DESIGN- SECTION 107.2.1 WPB. PLEASE NOTE
 THE FOLLOWING:
 ALL PLANS AND DOCUMENTS PREPARED BY A FL. LICENSED
 ENGINEER OR ARCHITECT ARE TO SIGNED, SEALED AND DATE
 ORIGINALS. PLANS TRANSMITTED ELECTRONICALLY SHALL BEAR
 THE DIGITAL SIGNATURES AND SEALS OF EITHER THE ENGINEER
 OR ARCHITECT- FL. STATUTES 471.025 & 481.221, AND FAC
 61G15-23.005 & 61G1-16.005.
 FL. LICENSED CONTRACTORS OR QUALIFIERS WHO PREPARE
 DRAWINGS SHALL PROVIDE HIS/HER SIGNATURE ON THEM-
 SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H)
 & 471.025. A TITLE BLOCK ON THE DRAWING THAT INCLUDES
 CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER IS ALSO
 REQUIRED.
  
 2) P-1: PLEASE PROVIDE A SHOWER PAN DETAIL- SECTIONS
 P2709.1 & P2709.2 FBC RES.
  
 3) P-1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE
 LISTING MAKE AND MODEL, GALLON SIZE AND EFFICIENCY
 RATING. THE DATA IN THE SCHEDULE SHALL MATCH THE DATA
 SHOWN ON THE ENERGY COMPLIANCE FORM R405-2020-
 50-GALLON & EFF 0.96- TABLE C404.2 FBC EC.
  
 4) P-1: THE RELIEF VALVE DISCHARGE PIPE SHALL TERMINATE
 NOT MORE THAN 6 INCHES AND NOT LESS THAN TWO TIMES THE
 DISCHARGE PIPE DIAMETER ABOVE THE FLOOR OR WASTE
 RECEPTOR FLOOD LEVEL RIM. THE DETAIL INCORRECTLY SHOWS
 THE DISCHARGE 4 INCHES FROM THE BOTTOM OF THE PAN NOT
 THE FLOOD LEVEL RIM.
  
 5) P-1: PROVIDE A THERMAL EXPANSION TANK AND SHOW THE
 LOCATION IN THE WATER HEATER DETAIL- SECTION P2903.4
 FBC RES.
  
 6) P-1: PROVIDE HEAT TRAPS FOR THE VERTICAL INLET AND
 OUTLET PIPE RISERS AT THE WATER HEATER- SECTION
 R403.5.5 FBC EC. PLEASE NOTE THE TRAPS ARE NOT REQUIRED
 IF THE WATER HEATER IS EQUIPPED WITH INTEGRAL HEAT
 TRAPS.
  
 7) PLEASE NOTE THAT WHERE A NEW POTABLE WATER SERVICE
 BACKFLOW PREVENTER IS REQUIRED: A FL. LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  