2021-04-14 12:46:00 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21031226 |
| 4/14/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P-1: THE PLAN SHEET DOES NOT BEAR THE NAME, |
| TITLE BLOCK, SIGNATURE OR SEAL OF THE PERSON WHO |
| PREPARED THE DESIGN- SECTION 107.2.1 WPB. PLEASE NOTE |
| THE FOLLOWING: |
| ALL PLANS AND DOCUMENTS PREPARED BY A FL. LICENSED |
| ENGINEER OR ARCHITECT ARE TO SIGNED, SEALED AND DATE |
| ORIGINALS. PLANS TRANSMITTED ELECTRONICALLY SHALL BEAR |
| THE DIGITAL SIGNATURES AND SEALS OF EITHER THE ENGINEER |
| OR ARCHITECT- FL. STATUTES 471.025 & 481.221, AND FAC |
| 61G15-23.005 & 61G1-16.005. |
| FL. LICENSED CONTRACTORS OR QUALIFIERS WHO PREPARE |
| DRAWINGS SHALL PROVIDE HIS/HER SIGNATURE ON THEM- |
| SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| & 471.025. A TITLE BLOCK ON THE DRAWING THAT INCLUDES |
| CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER IS ALSO |
| REQUIRED. |
| |
| 2) P-1: PLEASE PROVIDE A SHOWER PAN DETAIL- SECTIONS |
| P2709.1 & P2709.2 FBC RES. |
| |
| 3) P-1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE |
| LISTING MAKE AND MODEL, GALLON SIZE AND EFFICIENCY |
| RATING. THE DATA IN THE SCHEDULE SHALL MATCH THE DATA |
| SHOWN ON THE ENERGY COMPLIANCE FORM R405-2020- |
| 50-GALLON & EFF 0.96- TABLE C404.2 FBC EC. |
| |
| 4) P-1: THE RELIEF VALVE DISCHARGE PIPE SHALL TERMINATE |
| NOT MORE THAN 6 INCHES AND NOT LESS THAN TWO TIMES THE |
| DISCHARGE PIPE DIAMETER ABOVE THE FLOOR OR WASTE |
| RECEPTOR FLOOD LEVEL RIM. THE DETAIL INCORRECTLY SHOWS |
| THE DISCHARGE 4 INCHES FROM THE BOTTOM OF THE PAN NOT |
| THE FLOOD LEVEL RIM. |
| |
| 5) P-1: PROVIDE A THERMAL EXPANSION TANK AND SHOW THE |
| LOCATION IN THE WATER HEATER DETAIL- SECTION P2903.4 |
| FBC RES. |
| |
| 6) P-1: PROVIDE HEAT TRAPS FOR THE VERTICAL INLET AND |
| OUTLET PIPE RISERS AT THE WATER HEATER- SECTION |
| R403.5.5 FBC EC. PLEASE NOTE THE TRAPS ARE NOT REQUIRED |
| IF THE WATER HEATER IS EQUIPPED WITH INTEGRAL HEAT |
| TRAPS. |
| |
| 7) PLEASE NOTE THAT WHERE A NEW POTABLE WATER SERVICE |
| BACKFLOW PREVENTER IS REQUIRED: A FL. LICENSED PLUMBING |
| CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |