Plan Review Notes For Permit 21031226 |
Permit Number |
21031226 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-09 15:17:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) NO SMOKE ALARMS SHOWN ON PLAN. R314/315 | | | | 2) OUTLET SPACING IN THE MIDDLE BEDROOM IS NOT TO CODE | | 210.52 | | | | 3) PLEASE INDICATE ON THE DRAWINGS THE LOCATION OF THE | | PANEL. 215.5 |
|