2021-09-17 14:20:56 | COMMERCIAL ALTERATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE ROOF SLOPE TO COMPLY WITH FBC |
| 1507.10.1 SLOPE. |
| BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS |
| THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) FOR DRAINAGE, EXCEPT FOR COAL-TAR |
| BUILT-UP ROOFS THAT SHALL HAVE A DESIGN SLOPE OF NOT |
| LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (1-PERCENT SLOPE). |
| |
| 2) DOORS MARKED (E) = A 32" DOOR DOES NOT PROVIDE THE |
| CORRECT OPENING WIDTH FBC ACCESSIBILITY 404.2.3 CLEAR |
| WIDTH. |
| DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES |
| (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH |
| SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| FBC ACCESSIBILITY 203.9 EMPLOYEE WORK AREAS. |
| SPACES AND ELEMENTS WITHIN EMPLOYEE WORK AREAS SHALL |
| ONLY BE REQUIRED TO COMPLY WITH 206.2.8, 207.1, AND |
| 215.3 AND SHALL BE DESIGNED AND CONSTRUCTED SO THAT |
| INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER, AND |
| EXIT THE EMPLOYEE WORK AREA. |
| |
| 3) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS, DOORS |
| AND ROOFING SYSTEMS. |
| |
| 4) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE |
| LISTED BY PERMIT NUMBER ON THE DRAWINGS. |
| |
| 5) PLEASE SHOW THE WIND DESIGN CRITERIA USED (WIND |
| SPEED, RISK CATEGORY, EXPOSURE ETC.) PER FBC 1603.1.4 |
| |
| 6) PLEASE SHOW ACCESSIBLE PARKING AND ACCESS AISLE |
| DIMENSIONS TO COMPLY WITH FBC ACCESSIBILITY 502 |
| |
| 7) PLEASE SHOW THE ACCESSIBLE RESTROOM DETAILS PER FBC |
| ACCESSIBILITY CHAPTER 6 - SHOW GRAB BAR HEIGHTS, |
| LENGTHS AND LOCATIONS, SHOW MIRROR HEIGHT TO THE |
| REFLECTING SURFACE, SHOW PAPER DISPENSER HEIGHTS AND |
| DISTANCE FROM WATER CLOSETS ETC.. |
| |
| 8) JOB COST NEEDS TO BE SHOWN ON THE REVISED BUILDING |
| PERMIT APPLICATION. |
| |
| |