Plan Review Notes
Plan Review Notes For Permit 21031225
Permit Number 21031225
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-08 12:52:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21031225
 4/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-1: PROVIDE PLUMBING PLANS FOR THE ALTERED
 TOILET ROOM IN COMPLIANCE WITH SECTIONS 107.2.1 AND
 107.3.5.3.1 WPB, AND FBC- 2020 PLUMBING. PROVIDE THE
 FOLLOWING LIST OF ITEMS:
  
 A) SANITARY DRAINAGE AND WATER RISER DRAWINGS.
  
 B) PLUMBING FLOOR PLAN LAYOUT DRAWING.
  
 C) PLUMBING FIXTURE SCHEDULE.
  
 2) A-1: THE PROPOSED PROJECT SHALL BE IN COMPLIANCE
 WITH THE FBC-2020 EXISTING BUILDING CODE. PLEASE REFER
 TO SECTION 301.1 AND INDICATE WHICH COMPLIANCE METHOD
 WILL BE USED- PRESCRIPTIVE, WORK AREA, OR PERFORMANCE.
 A COMPLETE REVIEW CANNOT BE COMPLETED UNTIL A METHOD IS
 CHOSEN AND PLANS ARE REVISED IN ACCORDANCE WITH THE
 COMPLIANCE METHOD.
  
 3) A-1: THE CURRENT TOILET ROOM DESIGN IS INCOMPLETE
 AND NOT IN COMPLIANCE WITH THE FBC- 2020 ACCESSIBILITY
 CODE. REFER TO SECTIONS 202.3, 213.1, AND 213.3.1 FBC
 ACC AND PROVIDE ENLARGED TOILET ROOM DRAWINGS SHOWING
 COMPLIANCE WITH THE FOLLOWING ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION
 604.6.
 I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 4) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  