Plan Review Notes For Permit 21031225 |
Permit Number |
21031225 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-05 15:23:57 | PLAN DENIED | | 1) HEAT LOAD REQUIRED SECTION C 403.2.1 FLORIDA ENERGY | | CODE 2020 | | 2) EQUIPMENT SCHEDULE REQUIRED ON PLAN SECTION 107 FBC | | 3) SHOW LOCATION OF A/C CONDENSERS ON PLAN. SECTION 107 | | FBC | | 4) REFER TO SECTION 307.2.4.1 DUCTLESS MINI SPLIT | | SYSTEM TRAPS 2020 FBC (M) | | 5) PROVIDE OUTDOOR AIR CALCULATION PER TABLE 403.3.1.1 | | MINIMUM VENTILATION RATES | | 2020FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|