Plan Review Notes
Plan Review Notes For Permit 21031225
Permit Number 21031225
Review Stop M
Sequence Number 1
Notes
Date Text
2021-04-05 15:23:57PLAN DENIED
 1) HEAT LOAD REQUIRED SECTION C 403.2.1 FLORIDA ENERGY
 CODE 2020
 2) EQUIPMENT SCHEDULE REQUIRED ON PLAN SECTION 107 FBC
 3) SHOW LOCATION OF A/C CONDENSERS ON PLAN. SECTION 107
 FBC
 4) REFER TO SECTION 307.2.4.1 DUCTLESS MINI SPLIT
 SYSTEM TRAPS 2020 FBC (M)
 5) PROVIDE OUTDOOR AIR CALCULATION PER TABLE 403.3.1.1
 MINIMUM VENTILATION RATES
 2020FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676