Plan Review Notes For Permit 21031179 |
Permit Number |
21031179 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-04-27 16:06:46 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PAGE 19 OF 25 (ULTIMATE DESIGN WIND | | SPEED) IDENTIFIED/HIGHLIGHTED ON THE NEMO REPORT | | INDICATES AN ULTIMATE DESIGN WIND SPEED-VULT OF 140 | | MPH. THIS SHOULD BE AT 170 MPH. PLEASE REVIEW ALL | | SUBMITTED DOCUMENTS AND INDICATE THE SYSTEMS/ OPTIONS | | THAT WILL BE USED. |
|