Plan Review Notes
Plan Review Notes For Permit 21031169
Permit Number 21031169
Review Stop P
Sequence Number 3
Notes
Date Text
2021-07-23 09:24:353RD REVIEW FBC-2020 PLUMBING
 PERMIT-21031169
 7/23/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. NEW PLANS HAVE BEEN
 SUBMITTED BY A NEW DESIGN PROFESSIONAL. 1ST REVIEW OF
 NEW PLAN COMMENTS BELOW.
  
 1) SHEET P-201: THE NEW SANITARY DOES NOT SHOW PROPER
 VENTING OF THE NEW BATHROOM FIXTURES. THE DRAWING SHOWS
 TWO BATHROOM BRANCH DRAINS CONNECTING AT THE BASE OF A
 SOIL STACK. NO INDIVIDUAL OR COMMON VENTS FOR FIXTURE
 DRAINS, OR TYPICAL HORIZONTAL WET VENTING SYSTEMS ARE
 SHOWN. PLEASE REVIEW SECTIONS P3106, P3107, AND P3108
 FBC RES. AND CORRECT THE PLAN AND ISOMETRIC DRAWING.
  
 2) P-201 SHOWER PAN DETAIL: A) CORRECT THE 1/8 INCH
 SHOWER SLOPE SHOWN IN THE DETAIL TO INDICATE THE
 FINISHED FLOOR SLOPE SHALL NOT BE LESS THAN 1/4 INCH
 PER FT. AND NOT MORE THAN 1/2 INCH PER FT. PER SECTION
 P2709.1 FBC P. B) MISSING FROM THE DETAIL IS THE
 REQUIRED SHOWER PAN LINER- SECTIONS P2709.2- P2709.3.1
 FBC P. C) A FLOOR DRAIN IS NOT AN APPROVED SHOWER
 RECEPTOR- SECTIONS P2709.4 FBC P.
  
 3) P-201: PLEASE ADD A NOTE TO THE SLAB REPAIR DETAIL
 INDICATING THE EXPOSED SOIL WILL BE TERMITE TREATED-
 SECTION R318 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  