Date |
Text |
2021-07-23 09:24:35 | 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT-21031169 |
| 7/23/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. NEW PLANS HAVE BEEN |
| SUBMITTED BY A NEW DESIGN PROFESSIONAL. 1ST REVIEW OF |
| NEW PLAN COMMENTS BELOW. |
| |
| 1) SHEET P-201: THE NEW SANITARY DOES NOT SHOW PROPER |
| VENTING OF THE NEW BATHROOM FIXTURES. THE DRAWING SHOWS |
| TWO BATHROOM BRANCH DRAINS CONNECTING AT THE BASE OF A |
| SOIL STACK. NO INDIVIDUAL OR COMMON VENTS FOR FIXTURE |
| DRAINS, OR TYPICAL HORIZONTAL WET VENTING SYSTEMS ARE |
| SHOWN. PLEASE REVIEW SECTIONS P3106, P3107, AND P3108 |
| FBC RES. AND CORRECT THE PLAN AND ISOMETRIC DRAWING. |
| |
| 2) P-201 SHOWER PAN DETAIL: A) CORRECT THE 1/8 INCH |
| SHOWER SLOPE SHOWN IN THE DETAIL TO INDICATE THE |
| FINISHED FLOOR SLOPE SHALL NOT BE LESS THAN 1/4 INCH |
| PER FT. AND NOT MORE THAN 1/2 INCH PER FT. PER SECTION |
| P2709.1 FBC P. B) MISSING FROM THE DETAIL IS THE |
| REQUIRED SHOWER PAN LINER- SECTIONS P2709.2- P2709.3.1 |
| FBC P. C) A FLOOR DRAIN IS NOT AN APPROVED SHOWER |
| RECEPTOR- SECTIONS P2709.4 FBC P. |
| |
| 3) P-201: PLEASE ADD A NOTE TO THE SLAB REPAIR DETAIL |
| INDICATING THE EXPOSED SOIL WILL BE TERMITE TREATED- |
| SECTION R318 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |