2021-05-14 16:30:27 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT-21031169 |
| 5/14/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) 2ND REQUEST FOR A SANITARY DRAINAGE AND VENT |
| ISOMETRIC DRAWING FOR THE KITCHEN AND BATHS- SECTION |
| 107.3.5.3 WPB. |
| |
| 2) 2ND REQUEST FOR A SLAB REPAIR DETAIL- SECTION |
| 107.2.1 WPB. |
| |
| 3) SHEET P201: 2ND REQUEST FOR THE PLUMBING CONTRACTOR |
| OR QUALIFIER WHO PREPARED THE REVISED PLUMBING DRAWINGS |
| TO PROVIDE HIS/HER PRINTED NAME, PROJECT ADDRESS, AND |
| WET SIGNATURE ON IT- SECTION 107.2.1 WPB, AND FLORIDA |
| STATUTES 471.003(2)(H) & 471.025. |
| |
| 4) NEW COMMENT- P201: THE NEW PLUMBING FLOOR PLAN |
| DRAWING SHOWS 2-INCH DRAINS FOR WATER CLOSETS WHICH |
| REQUIRE A MINIMUM 3-INCH DRAIN CONNECTION- SECTION |
| P2712.1 FBC RES. |
| |
| 5) P201: THE SANITARY BUILDING DRAIN APPEARS TO |
| TERMINATE AT A DEAD END AND DOES NOT CONNECT TO EITHER |
| A BUILDING DRAIN OR SEWER LINE- SECTION P3001.1 FBC |
| RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
2021-05-14 16:29:35 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT-21031169 |
| 5/14/2020 |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| PLAN REVIEW RESULTS: DENIED. |
| 1) 2ND REQUEST FOR A SANITARY DRAINAGE AND VENT |
| ISOMETRIC DRAWING FOR THE KITCHEN AND BATHS- SECTION |
| 107.3.5.3 WPB. |
| 2) 2ND REQUEST FOR A SLAB REPAIR DETAIL- SECTION |
| 107.2.1 WPB. |
| 3) SHEET P201: 2ND REQUEST FOR THE PLUMBING CONTRACTOR |
| OR QUALIFIER WHO PREPARED THE REVISED PLUMBING DRAWINGS |
| TO PROVIDE HIS/HER PRINTED NAME, PROJECT ADDRESS, AND |
| WET SIGNATURE ON IT- SECTION 107.2.1 WPB, AND FLORIDA |
| STATUTES 471.003(2)(H) & 471.025. |
| 4) NEW COMMENT- P201: THE NEW PLUMBING FLOOR PLAN |
| DRAWING SHOWS 2-INCH DRAINS FOR WATER CLOSETS WHICH |
| REQUIRE A MINIMUM 3-INCH DRAIN CONNECTION- SECTION |
| P2712.1 FBC RES. |
| 5) P201: THE SANITARY BUILDING DRAIN APPEARS TO |
| TERMINATE AT A DEAD END AND DOES NOT CONNECT TO EITHER |
| A BUILDING DRAIN OR SEWER LINE- SECTION P3001.1 FBC |
| RES. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |