2021-06-30 07:50:10 | 2ND REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21031167 |
| 6/30/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. COMMENTS NOT ADDRESSED |
| FROM THE 1ST REVIEW ARE LISTED BELOW. |
| |
| 1B) DELIVERY PRESSURE AT THE METER. (NOT PROVIDED). |
| |
| 1K) PIPE SIZING TABLES. (LOW PRESSURE SCHED-40 |
| GALVANIZED TABLE NOT PROVIDED). |
| |
| PLEASE NOTE TABLE 402.4(21) WAS SUBMITTED FOR LOW |
| PRESSURE PE PIPING. THE DRAWING SHOWS A NEW TEE AT THE |
| METER WHICH APPEARS TO INDICATE A 3/4- INCH MAIN PIPE. |
| USING THE RELATIVE TABLE FOR LOW PRESSURE SCHED-40 |
| GALVANIZED -TABLE G2413.4(1) [402.4(2) , THE 3/4- INCH |
| INCH MAIN PIPE AT THE METER IS UNDERSIZED FOR THE |
| INCREASED TOTAL BTU LOAD OF 795,000 AT A TOTAL |
| DEVELOPED LENGTH OF 49 FT- SECTIONS G2413.1 & G2413.4.1 |
| FBC RES, |
| |
| 3) SURVEY: PLEASE INDICATE THE REQUIRED 10 FT. |
| CLEARANCE FOR THE GENERATOR EXHAUST TO WINDOW AND DOOR |
| OPENINGS INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| NEW COMMENT. |
| 1) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF |
| THE CONTRACTOR OR QUALIFIER SHALL BE PROVIDED ON THE |
| GAS RISER DRAWING- SECTION 107.2.1 WPB, AND FLORIDA |
| STATUTES 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |