2021-05-07 07:30:36 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21031167 |
| 5/7/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE A COMPLETE GAS RISER DRAWING FOR THE |
| GENERATOR THAT INCLUDES ALL NEW AND EXISTING GAS PIPING |
| AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & |
| G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- |
| THE RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| REGULATORS MARKED UP OR HIGHLIGHTED TO SHOW THE |
| SELECTED MODEL, INPUT AND OUT PRESSURES AND PIPE SIZES, |
| AND ORIFICE SIZES- G2421.1 & G2421.2 FBC RES. |
| |
| 3) SURVEY: PLEASE INDICATE THE REQUIRED 10 FT. |
| CLEARANCE FOR THE GENERATOR EXHAUST TO WINDOW AND DOOR |
| OPENINGS INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |