2021-04-21 10:55:36 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21031164 |
| 4/21/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| NFPA 58 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULT: DENIED- REVIEW COMMENTS BELOW. |
| |
| 1) INSTALLATION OF THE LP TANK UNDER THE DRIVEWAY WILL |
| REQUIRE SUBMITTAL OF SPECIFIC INSTALLATION GUIDELINES |
| FROM THE TANK MANUFACTURER OTHERWISE THE TANK SHALL BE |
| RELOCATED- SECTION G2408.1 FBC RES. THE GUIDELINES |
| SHALL INDICATE HOW THE TANK LOCATED UNDER THE DRIVEWAY |
| WILL BE PROTECTED FROM VEHICULAR DAMAGE AND INCLUDE |
| SPECIFICATIONS AND INSTRUCTIONS FOR INSTALLATION OF AN |
| IMPACT AND LOAD RESISTANT, LISTED AND LABELED TANK LID |
| COVER- SECTION 6.8.6.1 (E) AND SECTION G2408.1 FBC RES. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| SECTION 5.2.1.1 NFPA 58. |
| |
| 3) PROVIDE A UG LP TANK INSTALLATION AND HOLD-DOWN |
| DETAIL SHOWING HOW THE TANK WILL BE ANCHORED TO PREVENT |
| FLOTATION, COLLAPSE, OR LATERAL MOVEMENT. PLEASE |
| INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE |
| BURIAL DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, |
| SIZES, AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND |
| THE TYPE OF PROTECTIVE SLEEVES FOR THE CABLES OR |
| STRAPS- SECTION 6.8.6.1 NFPA-58. PLEASE NOTE THE TANK |
| SHALL BE INSTALLED A MINIMUM OF 18 IN. BELOW GRADE. |
| |
| 4) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION |
| BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM |
| CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED |
| CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA |
| 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1. |
| |
| 5) GAS RISER: |
| A) LIST THE MAKES AND MODELS OF THE REGULATORS AND |
| SUBMIT MANUFACTURER'S SPECIFICATIONS MARKED UP TO SHOW |
| THE SELECTED MODELS, INLET AND OUTLET PRESSURES AND |
| PIPE SIZES- SECTION 6.10.1 NFPA 58. |
| B) CORRECT THE 360,000 BTU LOAD FOR THE 24 KW |
| GENERATOR. THE SPECS SHOW 306,000 BTU LOAD- 6.11.2 |
| C) SHOW THE REQUIRED FLEX CONNECTOR AT THE GENERATOR |
| AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION |
| 6.11.3.9 |
| D) LIST THE PIPE SIZING TABLES USED- SECTION 16.1 NFPA |
| 58 & SECTION G2413.4 FBC RES. |
| |
| 6) SURVEY: CORRECT THE 5 FT. GENERATOR CLEARANCE |
| DISTANCE TO OPENINGS INTO THE BUILDING. MINIMUM 10 FT. |
| CLEARANCE IS REQUIRED- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |