1 |
|
Notes |
Date |
Text |
2021-04-26 11:25:32 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY | | OPENINGS INTO THE BUILDING. R303.5.1 INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | 2) SUBMIT GENERATOR PAD AND GENERATOR TO PAD ANCHORING | | DETAILS. IF A PRE-FABRICATED GENERATOR PAD IS TO BE | | USED, SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC | | ENGINEERING. FBC 107.2.1 | | |
|