2021-04-26 11:25:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY
 OPENINGS INTO THE BUILDING. R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) SUBMIT GENERATOR PAD AND GENERATOR TO PAD ANCHORING
 DETAILS. IF A PRE-FABRICATED GENERATOR PAD IS TO BE
 USED, SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC
 ENGINEERING. FBC 107.2.1
  