Plan Review Notes
Plan Review Notes For Permit 21031154
Permit Number 21031154
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-04 14:06:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT REQUIRED COMPONENT AND CLADDING DESIGN
 PRESSURES FOR THE OPENINGS THAT HAVE BEEN PREPARED BY A
 FLORIDA LICENSED DESIGN PROFESSIONAL. THE DOCUMENTS ARE
 REQUIRED TO BE DIGITALLY SIGNED BY THE DESIGN
 PROFESSIONAL IF SUBMITTED ELECTRONICALLY AND THE DESIGN
 PROFESSIONAL'S ORIGINAL HANDWRITTEN SIGNATURE IF PAPER
 DOCUMENTS ARE SUBMITTED. FS 471 & FAC 61G15 /FS 481 &
 FAC 61G1
  
 2) ONE OR BOTH OF THESE CHURCH BUILDINGS MAY BE RISK
 CATEGORY III. THIS WILL NEED TO BE DETERMINED BY THE
 DESIGN PROFESSIONAL AND REFLECTED IN THE COMPONENT AND
 CLADDING PRESSURES. FBC BUILDING 1604.5
  
 3) SOME OF THESE DOORS MAY BE REQUIRED EXIT DOORS THAT
 ARE REQUIRED TO OPEN IN THE DIRECTION OF EXIT TRAVEL
 AND HAVE PANIC HARDWARE. SPECIFY THE SWING AND HARDWARE
 ON THE EXISTING DOORS AND THE REPLACEMENT DOORS. THEY
 CAN NOT BE ANY LESS RESTRICTIVE THAN THE EXISTING. FBC
 EXISTING BUILDING 704.1
  
 4) HI-LIGHT OR CIRCLE THE SPECIFIC DOOR SIZES, GLASS
 TYPE, DESIGN PRESSURE AND OTHER ITEMS THAT APPLY TO THE
 DOORS THAT WILL BE INSTALLED. FBC AMENDMENTS 107.2.1
  