 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SHOWER PAN DETAIL.
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1; P2709.3
 SHOWER PAN LINING INSTALLATION.
  
 2. P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND
 TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH
 CONTROL VALVES OF THE PRESSURE-BALANCE,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 USED FOR COMPLIANCE WITH THIS SECTION.
 NOTE: YOU MAY PLACE THIS ON YOUR PLAN.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.