Plan Review Notes For Permit 21031128 |
Permit Number |
21031128 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-20 13:55:33 | PLAN REVIEW / PLUMBING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE SHOWER PAN DETAIL. | | P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1; P2709.3 | | SHOWER PAN LINING INSTALLATION. | | | | 2. P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND | | TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH | | CONTROL VALVES OF THE PRESSURE-BALANCE, | | THERMOSTATIC-MIXING OR COMBINATION | | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A | | HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME | | A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET | | TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN | | 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE | | USED FOR COMPLIANCE WITH THIS SECTION. | | NOTE: YOU MAY PLACE THIS ON YOUR PLAN. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|