2021-04-20 13:23:54PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. WALL TYPE INSULATION R-VALUE IS MISSING FROM FORM
 405.
 2. WALL TYPE INSULATION IS MISSING FROM FORM 405 EPL
 CARD.
 3. EPL CARD SHALL BE SIGNED BY BUILDER.
 R101.5.1.1.1BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE CODE OFFICIAL TO DEMONSTRATE
 CODE COMPLIANCE BY THIS METHOD. ALTERNATIVELY, A
 FLORIDA RESCHECK COMPUTER PRINTOUT MAY BE SUBMITTED TO
 DEMONSTRATE COMPLIANCE BY SECTIONS R402, R403 AND R404.
  
 4. PROVIDE CONDENSATE DISPOSAL DETAIL.
 M1411.3 CONDENSATE DISPOSAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.