Plan Review Notes For Permit 21031115 |
Permit Number |
21031115 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-07 11:00:22 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT GENERATOR SLAB DETAILS AND SPECIFY THE TYPE, | | SIZE AND NUMBER OF FASTENERS THAT WILL BE USED TO | | ANCHOR THE GENERATOR TO THE SLAB. IF A PREFABRICATED | | SLAB WILL BE USED SUBMIT PRODUCT APPROVALS OR SIGNED | | AND SEALED SITE SPECIFIC ENGINEERING. FBC 107.2.1 | | | | 2) THE GENERATOR IS LOCATED IN AN AE FLOOD ZONE, WHICH | | IS A SPECIAL FLOOD HAZARD AREA. THE GENERATOR IS | | REQUIRED TO BE LOCATED AT OR ABOVE THE ELEVATION OF THE | | LIVING AREA OF THE HOUSE. FBC-R322.1.6 | | |
|