2021-04-07 11:00:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT GENERATOR SLAB DETAILS AND SPECIFY THE TYPE,
 SIZE AND NUMBER OF FASTENERS THAT WILL BE USED TO
 ANCHOR THE GENERATOR TO THE SLAB. IF A PREFABRICATED
 SLAB WILL BE USED SUBMIT PRODUCT APPROVALS OR SIGNED
 AND SEALED SITE SPECIFIC ENGINEERING. FBC 107.2.1
  
 2) THE GENERATOR IS LOCATED IN AN AE FLOOD ZONE, WHICH
 IS A SPECIAL FLOOD HAZARD AREA. THE GENERATOR IS
 REQUIRED TO BE LOCATED AT OR ABOVE THE ELEVATION OF THE
 LIVING AREA OF THE HOUSE. FBC-R322.1.6
  