2021-04-28 16:09:23 | 04/19/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| 1. A BUILDING PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. THIS PERMIT MUST BE SUBMITTED AS |
| A SUB ALONG WITH AN A ELECTRICAL. |
| |
| 2. PLEASE PROVIDE PLANS THAT SHOW THE WORK THAT IS |
| RELATED TO THE PROPOSED WORK PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. THE SINK AND LAV HAVE BEEN MOVED SO PLEASE PROVIDE A |
| PLUMBING RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| |
| 4. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |