Plan Review Notes
Plan Review Notes For Permit 21031023
Permit Number 21031023
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-11 09:38:23JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL11647-R6 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT; MIAMI-DADE
 NOA NO. 17-1221.05 PAGES 1-5 TO INCLUDE LIMITATIONS
 PAGE(S). SUBMITTED EVALUATION REPORT IS NOT VALID FOR
 PRODUCT APPROVAL FL11647-R6.
 2. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5259-R29 IS THE 2017 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA?S FOR THE PROPOSED
 ROOF UNDERLAYMENT SYSTEM TO BE USED. INCLUDE COVER
 PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 3. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1365-R8 IS NOT AN APPROVED TILE ADHESIVE AS
 PER THE EVALUATION REPORT MIAMI-DADE NOA NO.
 17-1221.05. PROVIDE A COMPLETE SET OF 2020 CODE VERSION
 PRODUCT APPROVALS/NOA'S FOR THE PROPOSED ROOFING TILE
 ADHESIVE TO BE USED.
 4. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL6332-R8 IS THE 2017 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA?S FOR THE PROPOSED
 ROOF TILE ADHESIVE TO BE USED. INCLUDE COVER PAGE,
 EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 5. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED
 HIP & RIDGE METAL TO BE USED.
 6. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S).
 7. WPB A 109.3 BUILDING PERMIT VALUATIONS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS.
 VALUE TO INCLUDE LABOR AND MATERIALS, ARCHITECTURAL AND
 DESIGN FEES, OVERHEAD AND PROFIT.
  