Plan Review Notes
Plan Review Notes For Permit 21031014
Permit Number 21031014
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-08 14:58:241ST REVIEW FBC-2020 PLUMBING
 PERMIT-21031014
 4/8/2019
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: PROVIDE A SCOPE OF WORK ON THE PLAN FOR
 THE REMODELED KITCHEN AND BATHS. PROVIDE A LIST OF
 FIXTURES, APPLIANCES, FAUCETS, VALVES AND PIPES BEING
 REPLACED OR RELOCATED- SECTION 107.2.1 WPB.
  
 2) P1.1: PROVIDE SHOWER PAN DETAILS- SECTION 421.5 FBC
 P.
  
 3) P1.1: PROVIDE SHOWER FLOOR AND WALL FINISH DETAILS
 AND DIMENSIONS- SECTION 421.4.1 FBC P.
  
 4) P1.1: ADD THE ICE MAKER DRAIN LINE TO THE ISOMETRIC
 DRAWING- SECTION 107.3.5.3.1 WPB.
  
 5) P1.1: PROVIDE WATER SUPPLY RISER DRAWING SHOWING THE
 TYPES AND SIZES OF WATER PIPES, POINTS OF HW AND CW
 CONNECTIONS, AND LOCATIONS OF WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS- SECTIONS 604.9, 607.1, AND
 608.3 FBC P.
  
 6) P1.1: REFER TO SECTION 1002.1 FBC P: VERIFY THE
 HORIZONTAL DISTANCE FROM THE CENTERLINE OF THE NEW
 SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE INLET OF
 THE EXISTING TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A
 NOTE ON THE PLAN INDICATING COMPLIANCE.
  
 7) P1.1: RELOCATING THE TUB AND SHOWER DRAIN OUTLETS
 MAY REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO
 LOCATE REINFORCING STEEL OR POST STRESSED FLOOR
 TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO VERIFY
 COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB.
  
 8) P1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR
 SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND
 APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 315.1 FBC P, AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  