2021-04-12 14:23:54 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21030992 |
| 4/12/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET GS-1: PLEASE SHOW A 2 IN. STANDPIPE AND A 3 |
| IN. VERTICAL STACK FOR THE WASHING MACHINE- SECTION |
| 406.2 FBC P. |
| |
| 2) GS-1: PROVIDE ELECTRIC AND GAS WATER HEATER |
| EQUIPMENT SCHEDULES LISTING MAKES AND MODELS, GALLON |
| SIZE FOR STORAGE TANKS, AND EFFICIENCY RATINGS- TABLE |
| C404.2 FBC EC. PLEASE NOTE THAT THE ENERGY COMPLOIANCE |
| FORM FOR THE GUEST HOUSE SHOWS A GAS WATER HEATER, |
| HOWEVER THE PLANS SHOW AN ELECTRIC WATER HEATER. |
| |
| 3) GS-1: PROVIDE SHOWER PAN DETAILS- SECTION P2709.1 & |
| P2709.2 FBC RES. |
| |
| 4) GS-1: PROVIDE AN ELECTRIC WATER HEATER PIPING DETAIL |
| SHOWING THE THERMAL EXPANSION TANK, PAN, AND PAN DRAIN |
| RUN AND DRAIN TERMINATION LOCATION- SECTIONS P2801.6 & |
| P2903.4 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |