2021-04-12 15:18:11 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 21030992 |
| 4/12/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET GS-1 GAS RISER: PROVIDE THE BRANCH LENGTH |
| MEASUREMENTS, CUT PIPE LENGTH MEASUREMENTS, AND THE |
| TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO |
| THE MOST REMOTE OUTLET- SECTION G2413.4.1 & G2413.4.2 |
| FBC RES. |
| |
| 2) GS-1 GAS RISER: LIST THE PIPE SIZING TABLES USED TO |
| DESIGN THE SYSTEM- SECTION G2413.4. |
| |
| 3) GS-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| TANKLESS WATER HEATERS, COOKTOP AND DRYER- SECTIONS |
| G2408.1, G2438.1 G2448.1. |
| |
| 4) GS-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| COOKTOP- SECTION G2407.1 |
| |
| 5) GS-1: INDICATE HOW MAKEUP AIR WILL BE PROVIDED FOR |
| THE GAS DRYER- SECTION G2439.5. |
| |
| 6) GS-1: PROVIDE ELEVATIONS VIEW OF THE TANKLESS WATER |
| HEATERS INDICATING INSTALLATION LOCATIONS AND CLEARANCE |
| DISTANCE MEASUREMENTS FROM GRADE, OVERHEAD |
| CONSTRUCTION, AND AIR INTAKES AND WINDOW AND DOOR |
| OPENINGS INTO THE BUILDING- SECTIONS G2427.1 & G2448.1. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |