2021-04-14 15:16:12 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: CITY POLICY REQUIRES A SEPERATE PERMIT FOR EACH |
| STRUCTURE ON AN INDIVIDUAL PARCELL. SUBMIT PERMIT |
| APPLICATION FOR GUEST HOUSE. ALL PLANS WILL REMAIN |
| UNDER MAIN HOUSE PERMIT 21030992. |
| SEPERATE INSPECTIONS WILL BE REQUIRED. SEPERATE C/O |
| WILL BE ISSUED. |
| |
| 1. PROVIDE FINISHED FLOOR ELEVATION. |
| R403.1.7.3 FOUNDATION ELEVATION. |
| ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| ALL LOCATIONS ON THE SITE. |
| |
| FINISHED FLOOR ELEVATIONS SHALL BE PLACED ON FOUNDATION |
| PLAN AND/OR FLOOR PLAN. |
| |
| 2. PROVIDE SITE DRAINAGE PLAN. |
| FBC R401.3 SITE DRAINAGE |
| PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| FBC R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| |
| 3. SOILS REPORT NOT REQUIRED. PROVIDE DENSITY TEST AT |
| FOUNDATION INSPECTION. |
| |
| REF. PRODUCT APPROVAL AFFIDAVIT FOR THE FOLLOWING: |
| |
| 4. THE FOLLOWING PRODUCT APPROVALS ARE MISSING THE |
| COVER LETTER. THE COVER SHEET PROVIDES THE APPROVAL |
| NUMBER, CODE VERSION, AND STATUS, FBC R 301. |
| FL17184.1 |
| |
| 5. THE FOLLOWING PRODUCT APPROVALS ARE NOT LISTED ON |
| THE PRODUCT APPROVAL AFFIDAVIT. DESIGNER SHALL REVIEW |
| AND APPROVE THE FOLLOWING: |
| FL16709-R7, FL6332-R9, FL11288-R18. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |