| BUILDING REVIEW DENIED: |
| |
| 1) OK, MODEL # RXSW200A3, 22KW, 445 POUNDS AS PER |
| SUBMITTED MANUAL. |
| |
| 2) NOT RESOLVED. PROVIDE DETAILS OF THE EXISTING |
| GENERATOR SLAB AND SPECIFY THE NUMBER, TYPE AND SIZE OF |
| THE FASTENERS THAT WILL BE USED TO ANCHOR THE GENERATOR |
| TO THE SLAB TO RESIST WIND LOADS. FBC AMENDMENTS |
| 107.2.1 |
| |
| 3) NOT RESOLVED. SHOW THAT THE GENERATOR IS LOCATED 5 |
| FEET FROM THE WALLS OF ANY BUILDING. FBC? FUEL GAS |
| 616.1 POWERED EQUIPMENT. PERMANENTLY INSTALLED |
| EQUIPMENT POWERED BY INTERNAL COMBUSTION ENGINES AND |
| TURBINES SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| MANUFACTURER?S INSTRUCTIONS AND NFPA 37. STATIONARY |
| ENGINE GENERATOR ASSEMBLIES SHALL MEET THE REQUIREMENTS |
| OF UL 2200. |
| |
| 4) NOT RESOLVED. SHOW THAT THE GENERATOR EXHAUST IS AT |
| LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. |
| FBC?R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY |
| OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS |
| THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS |
| CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, |
| STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. |
| |
| 5) NOT RESOLVED. THE VALUE FOR THIS PROJECT OF $2350.00 |
| APPEARS TO BE LOW. FOR PERMITTING PURPOSES THE |
| VALUATION IS REQUIRED TO INCLUDE THE COSTS OF THE |
| LABOR, MATERIALS, OVERHEAD AND PROFIT AS WOULD BE |
| CHARGED BY A CONTRACTOR. PROVIDE A COMPLETE SCOPE OF |
| WORK WITH A COST BREAKDOWN. FBC AMENDMENTS 109.3 |
| BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHEDDATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES |
| (MARSHALL?SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE?SUBMITTAL FORM. |
| |