2022-04-25 17:18:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. [SUBMIT DETAILED SPECIFICATIONS FOR
 THE GENERATOR MODEL THAT WILL BE INSTALLED.] SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR THE NEW GENERATOR.
 SPECIFY THE MODEL NUMBER AND KW OF THE NEW GENERATOR.
 FBC AMENDMENTS 107.2.1
  
 2) NOT RESOLVED. PROVIDE DETAILS OF THE EXISTING
 GENERATOR SLAB AND SPECIFY THE NUMBER, TYPE AND SIZE OF
 THE FASTENERS THAT WILL BE USED TO ANCHOR THE GENERATOR
 TO THE SLAB TO RESIST WIND LOADS. FBC AMENDMENTS
 107.2.1
  
 3) NOT RESOLVED. SHOW THAT THE GENERATOR IS LOCATED 5
 FEET FROM THE WALLS OF ANY BUILDING. FBC- FUEL GAS
 616.1 POWERED EQUIPMENT. PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION ENGINES AND
 TURBINES SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS AND NFPA 37. STATIONARY
 ENGINE GENERATOR ASSEMBLIES SHALL MEET THE REQUIREMENTS
 OF UL 2200.
  
 4) NOT RESOLVED. SHOW THAT THE GENERATOR EXHAUST IS AT
 LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING.
 FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 5) NOT RESOLVED. THE VALUE FOR THIS PROJECT OF $2350.00
 APPEARS TO BE LOW. FOR PERMITTING PURPOSES THE
 VALUATION IS REQUIRED TO INCLUDE THE COSTS OF THE
 LABOR, MATERIALS, OVERHEAD AND PROFIT AS WOULD BE
 CHARGED BY A CONTRACTOR. PROVIDE A COMPLETE SCOPE OF
 WORK WITH A COST BREAKDOWN. FBC AMENDMENTS 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  