Date |
Text |
2021-04-07 10:08:57 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| GENERATOR. SPECIFY THE MODEL NUMBER AND KW OF THE NEW |
| GENERATOR. FBC AMENDMENTS 107.2.1 |
| |
| 2) PROVIDE DETAILS OF THE EXISTING GENERATOR SLAB AND |
| SPECIFY THE NUMBER, TYPE AND SIZE OF THE FASTENERS THAT |
| WILL BE USED TO ANCHOR THE GENERATOR TO THE SLAB TO |
| RESIST WIND LOADS. FBC AMENDMENTS 107.2.1 |
| |
| 3) SHOW THAT THE GENERATOR IS LOCATED 5 FEET FROM THE |
| WALLS OF ANY BUILDING. FBC- FUEL GAS 616.1 POWERED |
| EQUIPMENT. PERMANENTLY INSTALLED EQUIPMENT POWERED BY |
| INTERNAL COMBUSTION ENGINES AND TURBINES SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S |
| INSTRUCTIONS AND NFPA 37. STATIONARY ENGINE GENERATOR |
| ASSEMBLIES SHALL MEET THE REQUIREMENTS OF UL 2200. |
| |
| 4) SHOW THAT THE GENERATOR EXHAUST IS AT LEAST 10 FEET |
| FROM ANY OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE |
| OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE |
| OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS |
| VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, |
| PARKING LOTS AND LOADING DOCKS. |
| |
| 5) THE VALUE FOR THIS PROJECT OF $2350.00 APPEARS TO BE |
| LOW. FOR PERMITTING PURPOSES THE VALUATION IS REQUIRED |
| TO INCLUDE THE COSTS OF THE LABOR, MATERIALS, OVERHEAD |
| AND PROFIT AS WOULD BE CHARGED BY A CONTRACTOR. PROVIDE |
| A COMPLETE SCOPE OF WORK WITH A COST BREAKDOWN. FBC |
| AMENDMENTS 109.3 BUILDING PERMIT VALUATION. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| |