Plan Review Notes
Plan Review Notes For Permit 21030965
Permit Number 21030965
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-25 10:56:01JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00
 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. PROVIDE THE FOLLOWING INFORMATION FOR MIAMI-DADE NOA
 NO.: 20-0414.11 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED CORRESPONDING TO ENGINEERS CALCULATIONS. COVER
 PAGE, EVALUATION REPORTS, LIMITATIONS PAGE AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING.
 3. FBC B 107.2.1. SUBMITTED FASTENER DENSITY
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED ARCHITECT,
 OR REGISTERED ROOF CONSULTANT DO NOT CORRESPOND WITH
 ADDRESS LISTED ON PERMIT APPLICATION. PROVIDE CORRECT
 SIGNED AND SEALED ROOF CALCULATIONS.