Plan Review Notes For Permit 21030951 |
Permit Number |
21030951 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-24 16:06:35 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2, THE IMAGES SUBMITTED UNDER THE TITLE | | FORM 100 MAIN HOUSE APPEAR TO SHOW MORE THAN (1) | | STRUCTURE WITH INDICATIONS OF BEING PART OF THIS PERMIT | | WHILE THE APPLICATION INDICATES MAIN HOUSE ONLY. PLEASE | | CLARIFY THE PROPOSED WORK. | | | | 2) FBC B 107.2, THE SUBMITTED SPECIFICATIONS FOR SNAP | | MAX FROM EXTREME METAL FABRICATORS METHOD "A" DOES NOT | | SHOW A RATING FOR 170 MPH (ZONE 3) WITHIN THE PROVIDED | | TABLES. PLEASE PROVIDE ANOTHER METHOD TO MEET THE | | WINDLOAD REQUIREMENTS FOR ZONE 3. |
|