Plan Review Notes For Permit 21030940 |
Permit Number |
21030940 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-04-02 10:38:21 | R2 UNIT PARTIAL DEMO | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) EXCEPTION #2 CANNOT BE USED FOR THE 19TH FLOOR - THE | | EXIT DISCHARGE WOULD BE ON THE GRADE LEVEL - FBC 202 | | DEFINITIONS - EXIT DISCHARGE. THAT PORTION OF A MEANS | | OF EGRESS SYSTEM BETWEEN THE TERMINATION OF AN EXIT AND | | A PUBLIC WAY. | | PLEASE SHOW HOW THE ELEVATOR HOISTWAY WILL REMAIN FIRE | | PROTECTED PER FBC 3006.3 HOISTWAY OPENING PROTECTION. | | WHERE SECTION 3006.2 REQUIRES PROTECTION OF THE | | ELEVATOR HOISTWAY DOOR OPENING, THE PROTECTION SHALL BE | | PROVIDED BY ONE OF THE FOLLOWING: SEE 3006.3 | | | | | | |
|