Plan Review Notes For Permit 21030898 |
Permit Number |
21030898 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-03-22 13:11:11 | THE CONNECTION TO A WATER | | SOURCE SHOULD BE BEFORE | | THE PRV. | | | | | | THE PRV IN A STAIRWELL | | HAS NO BEARING ON THIS INSTALLATION. | | | | TEST TO 200 PSI PER NFPA 13. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|