Plan Review Notes For Permit 21030827 |
Permit Number |
21030827 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-04-26 09:24:03 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) OUTLET SPACING TO MEET 210.52(A) | | | | (2) WALL SPACE. AS USED IN THIS SECTION, A WALL SPACE | | SHALL INCLUDE THE FOLLOWING: | | (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING | | SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE | | FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS, | | FIREPLACES, AND FIXED CABINETS THAT DO NOT HAVE | | COUNTERTOPS OR SIMILAR WORK SURFACES (2) THE SPACE | | OCCUPIED BY FIXED PANELS IN WALLS, EXCLUDING SLIDING | | PANELS | | (3) THE SPACE AFFORDED BY FIXED ROOM DIVIDERS, SUCH AS | | FREESTANDING BAR-TYPE COUNTERS OR RAILINGS | | |
|