2021-04-02 13:11:34 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21030827 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN |
| MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE |
| MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE |
| SPECIFIC PROJECT WHICH HE OR SHE INSTALLS. THE |
| MECHANICAL CONTRACTOR MUST BE THE ONE THAT SIZED THE |
| MECHANICAL EQUIPMENT AND DREW THE DRAWING FOR THE |
| MECHANICAL EQUIPMENT OR YOU MAY HAVE AN ENGINEER TO |
| DESIGN THE WORK. |
| |
| 2) PLEASE PROVIDE A MECHANICAL DRAWING OF THIS PROJECT |
| SHOWING THE MECHANICAL UNIT LOCATIONS, THE CONDENSING |
| UNIT LOCATION, THE CONDENSATION LINES AND DRAINAGE |
| TERMINATION LOCATION, THE DUCT WORK AND SIZES. 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |