Plan Review Notes
Plan Review Notes For Permit 21030814
Permit Number 21030814
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-27 10:56:01WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21030814
 ADD: 1801 S. FLAGLER DR. # 1405
 CONT: AOA CONSTRUCTION LLC
 TEL: 561-660-3504
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 27TH/ 2021
 ACTION: DENIED
 1) FLOOR PLAN:
 1A) CONTRACTOR DRAWN FLOOR PLAN. CERTIFICATION BY
 CONTRACTOR. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DREW THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 1B) THE SUBMITTED FLOOR PLAN DOES NOT GIVE THE LOCATION
 OF THE UNIT AS TO WHERE THIS UNIT FITS IN TO THE FLOOR
 PLATE OF THE BUILDING. WALL ZONES 4 & 5 CANNOT BE
 ESTABLISHED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED TO BE ABLE TO DETERMINE WALL ZONES.
 ENGINEERING EXPRESS WIND CHART FOR INTERIOR WALL ZONE
 IS HIGHLIGHTED BUT THERE IS NO FLOOR PLAN THIS UNIT
 LOCATION IN THE FLOOR PLATE. DOOR SCHEDULE IS TAKEN FOR
 A WALL ZONE 4 BUT NOT PROVEN.
  
 2) THE SLIDING GLASS DOOR NOA # SHEET 4/11 SHOWS
 PRESSURES PLEASE HIGHLIGHT THE HEIGHT, WIDTH AND
 ASSOCIATED PRESSURES ALSO HIGHLIGHT WHICH SILL HEIGHT
 WILL BE USED IN THIS APPLICATION. THANK YOU. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  