Plan Review Notes
Plan Review Notes For Permit 21030812
Permit Number 21030812
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-14 16:51:1304/14/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 THE CITY OF WEST PALM BEACH HAS NO RECORD OF EXISTING
 GAS. A COMPLETE EVALUATION OF ALL GAS EQUIPMENT WILL BE
 DONE, AND IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO
 CODE COMPLIANCE AT THE OWNER'S EXPENSE.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 3. PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020
 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 4. PLEASE SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FG SEC. 409.4,
 2017 FBC RES. SEC. G2420.4.
  
 7. THIS TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1.
  
 8. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC.
 G2413.
  
 9. PLEASE SHOW THE DISTANCE FROM THE DELIVERY POINT
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 10. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) OF THE
 SYSTEM ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 11. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR TANK-LESS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 12. PLEASE LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC
 RES. SECS. G2413.3, G2413.4, AND TABLES G2413.4 (1)
 THROUGH G2413.4 (21).
  
 13. PLEASE SUBMIT THE SIZING TABLE USED IN THE GAS
 SYSTEM DESIGN OR PLACE AN ISOMETRIC NOTE LISTING THE
 SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD USED
 IN THIS SYSTEM'S DESIGN PER THE 2020 FBC RES. SEC.
 G2413.3.
  
 14. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED TO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2020 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 15. IF A REGULATOR IS REQUIRED, PLEASE SUBMIT THE
 MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE BUILDING'S
 EXTERIOR SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2020 FBC RES. SEC. G2421.1.
  
 16. PLEASE SHOW VALVES, DRIP LEG, AND ALL UNIONS IN
 FRONT OF REGULATOR 1? OF EITHER SIDE PER THE 2020 FBC
 RES. SEC G2421.2.
  
 17. PIPES NOT IN CONDITION SPACE NEED TO BE INSULATED
 WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE 403.5.3, A
 NOTE IS OK TO PUT ON ISOMETRIC.
  
 18. IF THIS TANK-LEES HAS CONDENSATE NEEDS TO BE 1'
 AWAY FROM STRUCTURE PER THE 2020 FBC SEC. R318.5, A
 NOTE IS OK TO PUT ON ISOMETRIC.
  
 19. PLEASE SHOW ON THE HOUSE PLANS THE LOCATION OF THE
 TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  