Date |
Text |
2021-05-06 11:26:01 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX |
| |
| 1. FBC B 1609. PROVIDE A COMPLETE SET OF SIGNED AND |
| SEALED DESIGN PRESSURE CALCULATIONS FOR HIGH |
| RISE/COMMERCIAL BUILDINGS BY A FLORIDA REGISTERED |
| DESIGN PROFESSIONAL. |
| 2. FBC B 107.2.1 PROVIDE A SIGN AND SEALED ROOF |
| DRAINAGE PLAN THAT COMPLIES WITH SECTION 1503 OF THE |
| 2020 FBC-BUILDING AND CHAPTER 11 OF THE 2020 |
| FBC-PLUMBING. |
| 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| 4. WPB A 109.3 BUILDING PERMIT VALUATIONS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS. |
| VALUE TO INCLUDE LABOR AND MATERIALS, ARCHITECTURAL AND |
| DESIGN FEES, OVERHEAD AND PROFIT. |
| |